On 11/16/2022 Checked walk in freezer. Found oil all over the condenser indicating a Freon leak. Took unit apart and conducted a leak check. Found leak on suction line quick connect. Tried to tighten the connect but it was still leaking. Pumped system down. Cut out both liquid and suction line quick connect and replaced…
Read more
Repaired Unit with Coils Heavily Iced Up
On 11/14/2022 Checked walk-in cooler. Found that out he of the coils was heavily iced up. Removed ice with hot water to find that the drains were stopped up which caused the coils to freezer over. Cut both drain lines and found sludge in the lines. Ran water into drain lines until water came out…
Read more
Repaired Incomplete Install on a New Hoshi Ice Maker
On 11/11/2022 Customer was having some issues with an incomplete install on a new Hoshi ice maker. The bin switch was not installed and there was an unneeded crossmember blocking the switch from being put into place. With some help from the super on site we lifted the machine just high enough to remove the…
Read more
Added Fan Cycle Switch for Proper Function
On 11/07/2022 Unit was showing very low head pressure at low ambient temps. I topped the system off and did a leak check. I found no leaks but I did notice that there is no fan cycle switch on this dual fan system. When I disconnected power to one of the fans the pressures leveled…
Read more