Condenser filter plugged with debris and unit in need of cleaning. Cleaned filter and ran through chemical cleaning. Cleaned adjacent Oasis units filter also on 2/28/24 in Frisco Texas. Near Main Street Frisco, Texas 75034 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more
Condenser Fan Gave Out
Condenser fan gave out causing the unit to kick out on thermal overload. I had the fan motor in van so I replaced and returned to service on 2/27/24 in Allen Texas. Near EAST Stacey rd. Allen, Texas 75002 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more
Unit Was Not Making Ice When I Arrived
Unit was not making ice when I arrived. I noticed some boxes stacked on the unit next to the ice machine blocking airflow to the condenser. I removed the boxes and the pressure dropped to near 315psi. This is still high so I checked the condenser coil and found it very dirty. I blew it…
Read more
Disassembled Machine Cleaned and Sanitized
Disassembled machine cleaned and sanitized according to manufacturer specs. Will need to return with filter. Customer would like a 6 month Preventative maintenance Contract on 2/23/24 in Balch Springs Texas. Near Seagoville Rd Balch Springs, Texas 75180 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more