On 5/22/2023 checked the condenser and found unit was off, tested thermostat and found it to be bad, the stat would not adjust at all, replaced thermostat with a mechanical thermostat, unit pulled down to -10 without an issue in Richardson Texas. Near Kas Dr Richardson, Texas 75081 Check out the Areas We Serve and…
Read more
Replaced Valve Plates
On 5/18/2023 Replaced valve plates on the first compressor, (high) upon getting the high compressor going I got the low compressor to come on and found that it had bad valve plates also, picked up new valve plates and installed. No further issues found at this time in Addison Texas. Near Arapaho Road Addison, Texas…
Read more
Replaced a 40amp Contactor 208v
On 5/17/2023 upon investigation of the cooler I replaced a 40amp contactor 208v control and found the unit was wired improperly, wired unit properly and checked all proper operations. Unit is making temperature now in DESOTO Texas. Near Falcon Dr DESOTO, Texas 75115 Check out the Areas We Serve and jobs we are doing by…
Read more
reset the controller and went through set up
On 5/11/2023 reset the controller and went through set up, before it wouldn't adjust over 28degrees so product was constantly freezing, I took out the parameters and reset up controller to be adjustable like the cooler next to it, it is now set to 35 and store can adjust accordingly from 40 degrees to 32,…
Read more