On 6/27/2023 System was cycling off after 5 minutes, I cleaned condenser coil because the head pressure was high, the pressure went down in Mesquite Texas. Near North Belt Line Road Mesquite, Texas 75182 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more
Deep Cleaned it With Heavy Sanitizer
On 6/23/2023 System was extremely dirty so I took it apart and deep cleaned it with heavy sanitizer/descaler. I also noticed the water flow through the filter was reversed. Customer had extra length of hose some i was able to put it right. I put it back together and ran the machine through a descale…
Read more
Replaced with High Pressure Switch
On 6/21/2023 I recovered all the refrigerant from both stages of the system. I removed the low-pressure switch that was placed on the high side and replaced with high pressure switch and wired it in correctly. I pulled a deep vacuum on both stages. And charged them with 407c in Dallas Texas. Near Lyndon B…
Read more
Replaced the Expansion Valve and Confirmed
On 6/15/2023 I cycled the system when I arrived and found a high head pressure. I cleaned the condenser by blowing it out with nitrogen. The head pressure came down but the over all pressure was low. I added some refrigerant and cycled the system multiple times only to find it was making ice on…
Read more