Reinsulated the refrigeration pipe and sealed the hole on the roof. The drain line was leaking on 3/4/24 in Rowlett Texas. Near Rowlett Rd Rowlett, Texas 75088 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more
Condenser Filter Plugged with Debris
Condenser filter plugged with debris and unit in need of cleaning. Cleaned filter and ran through chemical cleaning. Cleaned adjacent Oasis units filter also on 2/28/24 in Frisco Texas. Near Main Street Frisco, Texas 75034 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more
Condenser Fan Gave Out
Condenser fan gave out causing the unit to kick out on thermal overload. I had the fan motor in van so I replaced and returned to service on 2/27/24 in Allen Texas. Near EAST Stacey rd. Allen, Texas 75002 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more
Unit Was Not Making Ice When I Arrived
Unit was not making ice when I arrived. I noticed some boxes stacked on the unit next to the ice machine blocking airflow to the condenser. I removed the boxes and the pressure dropped to near 315psi. This is still high so I checked the condenser coil and found it very dirty. I blew it…
Read more