On 11/07/2022 Unit was showing very low head pressure at low ambient temps. I topped the system off and did a leak check. I found no leaks but I did notice that there is no fan cycle switch on this dual fan system. When I disconnected power to one of the fans the pressures leveled out. I recommend a switch be added to the system for proper function during fluctuations in ambient temp in Desoto Texas.
Near Falcon Dr Desoto Texas 75115
Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/
Leave a comment