Condenser Coil was Plugged With Dust

On 1/6/2023 Checked break room refrigerator. Found that compressor was hot to the touch due to it being off on internal overload. This happened because the condenser coil was plugged with dust. Brushed dust off the coil and blew it out with nitrogen. Put a bag of ice on top of the compressor to cool it off faster. After cooldown, the compressor was trying to come on. Checked compressor with mega ohm meter which checked out good. Replaced hard start kit. Started unit and compressor came on and is pulling down temperature in Carrollton Texas.