On 12/20/2022 Checked ice machine. Found an alert that the water probe was at fault. Pulled water probe out and saw it was heavily scaled up. I cleaned and adjusted ice thickness probe, soaked it in nickel safe ice machine cleaner and wipe all dirt and scale off. Reinstalled water probe. While checking out the…
Read more
Replaced Capacitor on Walk In Cooler
On 12/19/2022 Checked walk-in cooler. When I first got on the roof the condenser was working normally. When the system cycled off and cycled back on the condenser was having trouble starting. Checked capacitor, found that it was bad. Replaced capacitor on walk in cooler and checked operation. Let the system cycle off and back…
Read more
Condenser Coil on Prep Table was Plugged With Dirt
On 12/16/2022 Checked prep table refrigerator. Found that the back of the unit was producing a lot of heat. Found that the condenser coil on Prep Table was plugged with dirt. Cleaned condenser and waited until temperature came down to set point in Dallas Texas. Near Dallas Pkwy Dallas, Texas 75240 Check out the Areas…
Read more
Changed Filter Dryer
On 12/06/2022 Completed a de-scaling of ice machine. When attempted to clean ice machine the refrigerant was not flowing causing the compressor the shut down on low pressure. Notice the filter drier was frosty at the bottom. Recovered Freon out of system. Changed filter drier. Recharged system in Plano Texas. Near W Park Blvd Plano,…
Read more