On 12/05/2022 Checked walk-in cooler. Found that cooler was not temping correctly. Went on roof and put gauges on the condenser. Found that it was cutting out on high head pressure due to the condenser motor not working. Acquired motor from supply house. Replaced condenser motor and checked operation. Cooler is working properly in Frisco…
Read more
Replaced Chiller Saddle Tap Installed on Suction Line
On 12/02/2022 Checked wine chiller. Found that a saddle tap was installed on the suction line. Tap was leaking with the set screw all the way now. Removed saddle tap and added a tap that has to be wielded in. Pulled vacuum on unit and added the appropriate amount of r134a in Frisco Texas. Near…
Read more
Repaired Leak on Copper Line
On 12/01/2022 I Checked a walk-in freezer and found that it was low on Freon. I completed a leak check and found a leak on the copper line. I repaired the leak and Added 5 lbs. of R404a. I Waited until freezer had dropped down to the set point in Frisco Texas. Near Lebanon rd…
Read more
Replaced a Bad Condenser Fan Motor
On 11/30/2022 We replaced a bad condenser fan motor and removed an unnecessary defrost time that had also failed in Haslet Texas. Near Santa Fe Court Haslet, Texas 76052 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]