On 11/16/2022 Checked walk in freezer. Found oil all over the condenser indicating a Freon leak. Took unit apart and conducted a leak check. Found leak on suction line quick connect. Tried to tighten the connect but it was still leaking. Pumped system down. Cut out both liquid and suction line quick connect and replaced with copper pipe. After pulling a vacuum on the lines. I open the service ports and started the condenser. Found that the fan cycle control switch would not activate after reaching 240 psi on the high side. Replaced fan cycle control. Started unit up and everything came on. Charge unit with 4lbs of R404a, flashing gone in sight glass. Temperature in freezer reaches set point in The Colony Texas.