On 5/26/2023 found the unit to be at 34 degrees, checked the condenser and found that the condenser coil was very dirty, causing the unit to run warmer when the ambient temperature rises. I cleaned the coil and restored proper air flow through condenser. Unit was at 34 degrees, no further issues found at this…
Read more
Replaced the Defrost Timer on the Condenser
On 5/25/2023 Replaced the defrost timer on the condenser with a 208v new clock in DESOTO Texas. Near Falcon Dr DESOTO, Texas 75115 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more
Found a Leak on the Fan Cycling Switch
On 5/24/20023 found the unit to be low on refrigerant, I found a leak on the fan cycling switch off the high pressure gas line, I tightened fitting and stopped leak, continued leak checking with a electronic, and visual bubbles, no other leaks found, I charged unit with 2lbs of R404A, unit dumped 3 batches…
Read more
Discharge ROTOLOK Fitting had Vibrated Loose
On 5/23/2023 started leak checking the Evaporator with electronic detector, no hits inside walk in, proceeded to condenser and found the discharge ROTOLOK fitting had vibrated loose and was leaking, I tightened the fitting and stopped the leak, I did find a small leak on the txv valve pick up screen that I tightened also,…
Read more