Found Both Units Off at the Breaker

Found both units off at the breaker, not tripped but off. I turned them back on the right-side cooler came down to temp fine. The left did not come on so I started tracing wiring and found a loose wire that had blown one of the buss fuses. I replaced both fuses and confirmed all wiring was correct and safe. Watched both units make temp and cycle properly on 11/22/23 in Dallas Texas.