Found Leak at the High-Pressure Control

Found leak at the high-pressure control connection. I tightened the fitting and confirmed there were no other leaks. I added 4# of 404a. I noticed that the second fan was not going off on the fan control setting causing the pressure to drop very low in the cooler weather. I checked the wiring and found that the fan control was not wired in at all. I wired it in and confirmed it was working properly. Unit was dropping below 10*f when I was cleaning up my tools. All systems should be good to go on10/23/2023 in Garland Texas.