On 8/1/2023 I checked the HVAC systems all functioning relatively well other than one being 25+ years old. I cleaned all condensers and immediately saw a drop in the head pressure as well as the water snide temp dropped 5-6* over about an hour’s time after struggling to make sub 80* temps in Allen Texas.…
Read more
Install New Compressor and Start Components
On 7/31/2023 Recover refrigerant, power off unit, disconnect electrical, remove compressor and start components, remove filter drier, install new compressor and start components, install new filter drier, pull 500 micron vacuum, charge system with 134a, power on unit and confirm proper function in Farmers Branch Texas. Near Medical Pkwy Farmers Branch, Texas 75234 Check out…
Read more
Found Pressures Too Low
On 7/28/2023 Arrived and started checking unit.. found pressures too low for 404a and started looking for leak...found two pinhole leaks on EVAP and soldered them .. added 2.5 lbs. of 404a to bring up pressures to 72/315 and felt box dropping temp and verified temp drop … For future reference I got model and…
Read more
Replacing Expansion Valves
On 7/26/2023 pumped down units and started replacing expansion valves. Had to move product around to get to valves but after replacing pulled a deep vacuum and started working on the big cooler. In the big cooler I adjusted fan speed for one motor and got temp to start dropping as one of the fans…
Read more